Post Insulators untuk voltan tinggi ANSI 01
Kunci kepada kejayaan kami ialah "Kualiti Baik Produk, Nilai yang berpatutan dan perkhidmatan yang cekap" untuk Polymer Pin penebat, Porcelain Insulator , Composite Post Insulator, Whether selecting a current product from our catalog or seeking engineering assistance for your application, you can talk to our customer service center about your sourcing requirements. We’ve been looking forward to cooperating with friends from all over the world.
DIMENSI UTAMA DAN MAKLUMAT STANDARD
Cat. Tiada |
H1301 |
H1302 |
H1303 |
H1304 |
H1305 |
H1306 |
||
Kelas |
57-1 |
57-2 |
57-3 |
57-4 |
57-5 |
57-6 |
||
ara |
1 |
1 |
1 |
2 |
2 |
2 |
||
frekuensi rendah voltan flashover |
Kering (kV) |
70 |
100 |
125 |
140 |
160 |
180 |
|
Basah (kV) |
50 |
70 |
95 |
110 |
130 |
150 |
||
Flashover Positif kritikal Impulse (kV) |
120 |
160 |
200 |
230 |
265 |
300 |
||
Radio-Pengaruh-Voltan Data |
Ujian Voltan (kV) |
15 |
22 |
30 |
44 |
44 |
44 |
|
Mac RIV 2 μV |
100 |
100 |
200 |
200 |
200 |
200 |
||
Mendedahkan Jarak (inci) |
14 |
22 |
29 |
40 |
45 |
53 |
||
Kering pengarkaan Jarak (inci) |
6.5 |
9.5 |
12.25 |
14.5 |
17.25 |
19.25 |
||
Rujuk tinggi (inci) yang |
9 |
12 |
15 |
17 |
20 |
23.5 |
||
Julur gagal beban (pound) |
2800 |
2800 |
2800 |
2800 |
2800 |
2800 |
||
Diameter taraf Insulators (inci) |
5.5 |
6 |
6.5 |
7 |
7.5 |
8 |
||
Pusat lubang standard dimensi thread (inci) |
3/4 |
3/4 |
3/4 |
3/4 |
3/4 |
7/4 |
Kita melihat kualiti sebagai asas perusahaan, mematuhi falsafah pengurusan yang untuk melakukan kurang produk dan jangan biarkan produk yang tidak berkelayakan meninggalkan kilang.